| Rating | : | 30 kVA, 3 Phase, 4 Wire |
| Output Current | : | 43 Amps per phase |
| Input Voltage Range | : | 340V to 460V, 47Hz to 63Hz, 4 Wire |
| Output Voltage | : | 400V +/- 1% |
| Duty Cycle | : | Continuous 24x7 |
| Response Time | : | Less than 10ms |
| Suitability | : | Suitable for all power factor loads |
| Cooling | : | Natural Oil Cooled |
| Class of Insulation | : | A Class |
| Breakdown Strength & IR | : | 1500V AC For 2 Minutes. Greater than 50 Mega Ohms at 500V DC |
| Additional Facility | : | Manual Operation |
| Installation | : | Indoor type (Out Door Type Also Available |
| No Load Loss | : | Less than 0.4% |
| Efficiency | : | 98-99% |
| Ambient Temperature | : | -20 deg C to +50 deg C |
| Transformer Oil | : | New Insulating Transformer Oil ISI 335 Marked |
| Size (in mm) & Weight | : | L 1040 x D 430 x H 790 & 240 Kg. |
| Input / Output Termination | : | On Copper Bus Bar |
| Winding & Wiring Material | : | Copper EC grade (99.9% Pure) |
| Technology | : | Torridly wound Variable Auto Transformer for linear control and greater efficiency. |
| Controls | : | All the three phases controlled individually for better voltage and load management. |
| Applicable Standard | : | IS 9815 , ISO 9001-2015 , ISO 14001-2015 |
| International Marking | : | CE Conformity EN61558-1:2005+A1:2009 |
Price: